Prévia do material em texto
Produkte Products Prüfbericht - Nr.: Test Report No.: 50286745 001 Auftrags-Nr.: Order No.: 244165550 Seite 1 von 21 Page 1 of 21 Kunden-Referenz-Nr.: Client Reference No.: 1616910 Auftragsdatum: Order date: 30.07.2019 Auftraggeber: Client: Ningbo Ginlong technologies Co., Ltd. No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, Ningbo, zhejiang, 315712, P.R. China Prüfgegenstand: Test item: Grid-connected PV Inverter Bezeichnung / Typ-Nr.: Identification / Type No.: Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G, Solis-3P10K-4G, Solis-3P12K-4G, Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G Auftrags-Inhalt: Order content: Test report Prüfgrundlage: Test specification: IEC 61000-3-12: 2011 Wareneingangsdatum: Date of receipt:: 04.08.2019 Prüfmuster-Nr.: Test sample No.: A000969098-001 Prüfzeitraum: Testing period: 05.08.2019 – 09.08.2019 Ort der Prüfung: Place of testing: TÜV Rheinland (Shanghai) Co., Ltd. Prüflaboratorium: Testing Laboratory: TÜV Rheinland (Shanghai) Co., Ltd. Prüfergebnis*: Test Result*: Pass geprüft/ tested by: kontrolliert/ reviewed by: Aug.,26, 2019 John Dai / PE Aug.,26, 2019 Yin Yue / Reviwer Datum Date Name/Stellung Name/Position Unterschrift Signature Datum Date Name/Stellung Name/Position Unterschrift Signature Sonstiges/ Other Aspects: See the following pages for General product information and comment. Zustand des Prüfgegenstandes bei Anlieferung: Condition of test item at delivery: Prüfmuster vollständig und unbeschädigt Test item complete and undamaged * Legende: 1 = sehr gut 2 = gut 3 = bef riedigend 4 = ausreichend 5 = mangelhaf t P(ass) = entspricht o.g. Prüfgrundlage(n) F(ail) = entspricht nicht o.g. Prüf grundlage(n) N/A = nicht anwendbar N/T = nicht getestet Legend: 1 = very good 2 = good 3 = satisfactory 4 = sufficient 5 = poor P(ass) = passed a.m. test specification(s) F(ail) = failed a.m. test specification(s) N/A = not applicable N/T = not tested Dieser Prüfbericht bezieht sich nur auf das o.g. Prüfmuster und darf ohne Genehmigung der Prüfstelle nicht auszugsweise vervi elfältigt werden. Dieser Bericht berechtigt nicht zur Verwendung eines Prüfzeichens. This test report only relates to the a. m. test sample. Without permission of the test center this test report is not permitt ed to be duplicated in extracts. This test report does not entitle to carry any test mark. V04 TUV Rheinland (Shanghai) Co., Ltd. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jingan District, Shanghai 200072, P.R. China Tel. : +86 21 61081188 Fax : +86 21 61081199 Mail: service@cn.tuv.com Web: www.tuv.com Electromagnetic Compatibility (EMC) Part 3-12: Limits-Limits for harmonic current produced by equipment connected to public low-voltage systems with input current > 16A and ≤75A per phase Report Reference No. ................. : 50286745 001 Tested by (name + signature)....... : See cover page .............................................. Witnessed by (name + signature).. : See cover page .............................................. Supervised by (name + signature). : See cover page .............................................. Approved by (name + signature) ... : See cover page .............................................. Date of issue ............................. : See cove page Testing Laboratory...................... : TÜV Rheinland (Shanghai) Co., Ltd. Address .................................... : No. 177, Lane 777 West Guangzhong Road, Jingan District, Shanghai, P.R.China Testing location/ procedure .......... : CBTL TMP WMT SMT RMT CCATL Testing location/ address ............. : TÜV Rheinland (Shanghai) Co., Ltd. No. 177, Lane 777 West Guangzhong Road, Jingan District, Shanghai, P.R.China Applicant’s name ........................ : Ningbo Ginlong technologies Co., Ltd. Address .................................... : No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, Ningbo, zhejiang, 315712, P.R. China Test specification: Standard ................................... : IEC 61000-3-12: 2011 Test procedure........................... : TR Non-standard test method………..: N/A Test Report Form No. ................. : MS-0024873-appendix 17 V.0 Test Report Form(s) Originator ..... : TÜV Rheinland Group Master TRF ............................... : 2017-08 Test item description ................... : Grid-connected PV Inverter Trade Mark................................ : Manufacturer ............................. : Same as the applicant Model/Type reference ................. : Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G,Solis-3P10K-4G, Solis-3P12K-4G, Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G Ratings ..................................... : See copy of marking plate for details www.tuv.com Page 3 of 21 Report No.: 50286745 001 TRF No. MS-0024873-appendix 17 V.0 Equipment mobility ............................................ : movable hand-held stationary fixed Connection to the mains ..................................... : pluggable equipment direct plug-in permanent connection for building-in Operating condition............................................ : continuous short-time intermittent Over voltage category Mains ............................... : OVC I OVC II OVC III OVC IV Over voltage category PV ................................... : OVC I OVC II OVC III OVC IV Mains supply tolerance (%) ................................. : -- Tested for IT power systems .............................. : Yes No IT testing, phase-phase voltage (V) ..................... : N/A Class of equipment ........................................... : Class I Class II Class III Not classified Mass of equipment (kg) ...................................... : -- Pollution degree ................................................ : PD 1 PD 2 PD 3 IP protection class ............................................ : IP65 Possible test case verdicts: - test case does not apply to the test object ............. : N/A - test object does meet the requirement .................. : Pass (P) - test object does not meet the requirement ............. : Fail (F) Testing: Date of receipt of test items ................................. : See cover page Date(s) of performance of tests ............................. : See cover page Page 4 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 General remarks ” The test result presented in this report relate only to the object(s) tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see remark #)" refers to remark appended to the report. "(see Annex #)" refers to an annex appended to the report. Throughout this report a point is used as the decimal separator. General product information: The PCEs under test models Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G, Solis-3P10K- 4G, Solis-3P12K-4G, Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G are three-phase grid connected inverter for solar power generation. The Grid-connected PV Inverter utilize the advanced power conversion technology IGBT to convert the DC power normally from the photovoltaic array to stable three-phase AC power and then feed the power to the utility grid. Block diagram: www.tuv.com Page 5 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 Model list MODELS LIST Solis-3P5K-4G Solis-3P6K-4G Solis-3P8K-4G IN P U T VMAX PV[Vdc] 1000 ISC PV [A] 17.2+17.2 MPP Voltage Range VMPP[Vdc] 160-850 160-850 160-850 Max. Input Current Imax [A] 11+11 11+11 11+11 MPP Full Pow er Voltage Range [Vdc] 230-850 280-850 370-850 Start PV Voltage [Vdc] 180 180 180 Backfeed Current [A] 0 0 0 Overvoltage Category (OVC) II O U T P U T Rated Output Voltage Ur [Vac] 400V Rated Output Frequency FNETZ [Hz] 50/60 Rated Output Pow er PE [W] 5000 6000 8000 Max. Output Pow er PEmax [W] 5500 6600 8800 Max. Output Current Imax [A] 7.9 9.5 12.7 Pow er Factor cosφ [λ] [-0.8, 0.8] Night Pow er Consumption [W] <1 THD [V / I] (100% full pow er) < 3% Acoustic Noise [dB] < 30 Overvoltage Category (OVC) III S Y S T E M Protective Class I Enclosure Protection (IP) IP65 Operating Temperature Range [ºC] -25 to +60 Pollution degree (PD) PD 2 Altitude [m] 2000 Array Insulation Resistance Detection [Ω] 80k The accuracy of resistance measurement [%] < 10 Weight [kg] 17.3 17.3 18.0 Size [mm] 563W*310H*219D Firmw are version LCD: 05 DSP: 18 www.tuv.com Page 6 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 MODELS LIST Solis-3P9K-4G Solis-3P10K-4G IN P U T VMAX PV [Vdc] 1000 ISC PV [A] 17.2+17.2 MPP Voltage Range VMPP[Vdc] 160-850 160-850 Max. Input Current Imax [A] 11+11 11+11 MPP Full Pow er Voltage Range [Vdc] 415-850 465-850 Start PV Voltage [Vdc] 180 180 Backfeed Current [A] 0 0 Overvoltage Category (OVC) II O U T P U T Rated Output Voltage Ur [Vac] 400V Rated Output Frequency FNETZ [Hz] 50/60 Rated Output Pow er PE [W] 9000 10000 Max. Output Pow er PEmax [W] 9900 11000 Max. Output Current Imax [A] 14.3 15.9 Pow er Factor cosφ [λ] [-0.8, 0.8] Night Pow er Consumption [W] <1 THD [V / I] (100% full pow er) < 3% Acoustic Noise [dB] < 30 Overvoltage Category (OVC) III S Y S T E M Protective Class I Enclosure Protection (IP) IP65 Operating Temperature Range [ºC] -25 to +60 Pollution degree (PD) PD 2 Altitude [m] 2000 Array Insulation Resistance Detection [Ω] 80k The accuracy of resistance measurement [%] < 10 Weight [kg] 18.0 18.0 Size [mm] 563W*310H*219Dmm Firmw are version LCD: 05 DSP: 18 www.tuv.com Page 7 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 MODELS LIST Solis -3P12K-4G Solis -3P15K-4G IN P U T VMAX PV [Vdc] 1000 ISC PV [A] 34.3+34.3 MPP Voltage Range VMPP[Vdc] 160-850 160-850 Max. Input Current Imax [A] 22+22 22+22 MPP Full Pow er Voltage Range [Vdc] 280-850 350-850 Start PV Voltage [Vdc] 180 180 Backfeed Current [A] 0 0 Overvoltage Category (OVC) II O U T P U T Rated Output Voltage Ur [Vac] 400V Rated Output Frequency FNETZ [Hz] 50/60 Rated Output Pow er PE [W] 12000 15000 Max. Output Pow er PEmax [W] 13200 16500 Max. Output Current Imax [A] 19.1 23.8 Pow er Factor cosφ [λ] [-0.8, 0.8] Night Pow er Consumption [W] <1 THD [V / I] (100% full pow er) < 3% Acoustic Noise [dB] < 30 Overvoltage Category (OVC) III S Y S T E M Protective Class I Enclosure Protection (IP) IP65 Operating Temperature Range [ºC] -25 to +60 Pollution degree (PD) PD 2 Altitude [m] 2000 Array Insulation Resistance Detection [Ω] 80k The accuracy of resistance measurement [%] < 10 Weight [kg] 18.9 18.9 Size [mm] 563W*310H*219D Firmw are version LCD: 05 DSP: 18 www.tuv.com Page 8 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 MODELS LIST Solis -3P17K-4G Solis -3P20K-4G IN P U T VMAX PV [Vdc] 1000 ISC PV [A] 34.3+34.3 MPP Voltage Range VMPP[Vdc] 160-850 160-850 Max. Input Current Imax [A] 22+22 22+22 MPP Full Pow er Voltage Range [Vdc] 395-850 465-850 Start PV Voltage [Vdc] 180 180 Backfeed Current [A] 0 0 Overvoltage Category (OVC) II O U T P U T Rated Output Voltage Ur [Vac] 400V Rated Output Frequency FNETZ [Hz] 50/60 Rated Output Pow er PE [W] 17000 20000 Max. Output Pow er PEmax [W] 18700 22000 Max. Output Current Imax [A] 27 31.8 Pow er Factor cosφ [λ] [-0.8, 0.8] Night Pow er Consumption [W] <1 THD [V / I] (100% full pow er) < 3% Acoustic Noise [dB] < 30 Overvoltage Category (OVC) III S Y S T E M Protective Class I Enclosure Protection (IP) IP65 Operating Temperature Range [ºC] -25 to +60 Pollution degree (PD) PD 2 Altitude [m] 2000 Array Insulation Resistance Detection [Ω] 80k The accuracy of resistance measurement [%] < 10 Weight [kg] 19.8 19.8 Size [mm] 563W*310H*219D Firmw are version LCD: 05 DSP: 18 Factory: Ningbo Ginlong technologies Co., Ltd. No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, Ningbo, zhejiang, 315712, P.R. China www.tuv.com Page 9 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 Summary of testing: Tests performed (name of test and test clause) Clause(s) Test(s) Model(s) cl. 4.2 Harmonic current measurement Solis-3P20K-4G Testing location: All tests as described in Test Case and Measurement Sections were performed at the laboratory described on page 2. www.tuv.com Page 10 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 Copy of marking plate: www.tuv.com Page 11 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 www.tuv.com Page 12 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 www.tuv.com Page 13 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 www.tuv.com Page 14 of 21 Report No: 50286745 001 MS-0024873-appendix 17 V.0 www.tuv.com Page 15 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 IEC 61000-3-12: 2011 Clause Requirement – Test Result - Remark Verdict 4 Measurement conditions p 4.1 The average r.m.s input current shall be measured using the averaging method defined in 4.2.2 for harmonic current. P The manufacture may specify any value of r.m.s. current which is within ± 10% of the actual measured value and use it as the reference current. P If the value of the average r.m.s. input current found by measurement during these emission tests, measured according to the terms of this clause , is not less than 90% nor greater than110% of the value of current specified by manufacture. P 4.2 Harmonic current measurement P 4.2.1 The harmonic current limits for equipment as specified apply to the line currents for all types of power connections and load. P 4.2.2 The measurement of harmonic current shall be performance as follows: - For each harmonic order, measure 1.5s smooth r.m.s. harmonic current in each discrete fourier time winding as defined in IEC 61000-4-7. - For each harmonic order, calculate the arithmetic average of the measured value from the DFT time windows, over the entire test observation period as defined in 4.2.7. P 4.2.3 The repeatability of the average value for the individual harmonic current over the entire test abservation period shall be better than ±5% of the applicable limit. P 4.2.4 Equipment is operation or is taken out of operation manually or automatically, harmonic currents are not taken into account for the first 10s, or until the equipment is fully in or out of operation. P 4.2.5 The average value for the individual harmonic currents, taken over the entire test observation period shall be less than or equal to the applicable limits in table 2 to 5. P 5 Requirements and limits for equipment P 5.1 Only symmetrical control methods are allowed under normal operation conditions. P 5.2 The limits given apply to 230/240V, 50Hz systems, The limits for the other systems will be added in a future edition of this standard. P 6 Product documentationP www.tuv.com Page 16 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 IEC 61000-3-12: 2011 Clause Requirement – Test Result - Remark Verdict 7 Test and simulation conditions P 7.1 Conformity with this standard may be determined by either of the two methods as follows: a) Direct measurement (see 7.2) b) Calculation by validated simulation (see 7.3) P 7.2 The requirements for the measurement instrumentation are given in IEC 61000-4-7. P 7.3 Requirements for simulation P 7.4 General conditions for test and simulation P Annex A Type test conditions P Annex B Illustration of limits for harmonic currents P Annex C Equipment not complying with the requirements and limit of this standard N/A Annex D Information on the PWHD factor P Bibliography -- N/A www.tuv.com Page 17 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 4.2 Harmonic current (Solis-3P20K-4G) P Watts 20000W VA 20000VA Vrms 400V Arms 28.9A PF 1.00 Frequency(Hz) 50 Harmonic Measurement value(%) Limit (%) 2nd 0.5164 8 3rd 0.5312 21.6 4th 0.4949 4.00 5th 0.9133 10.70 6th 0.2351 2.67 7th 0.6774 7.20 8th 0.2632 2.00 9th 0.1361 3.80 10th 0.1362 1.60 11th 0.2580 3.10 12th 0.1525 1.33 13th 0.3749 2.00 14th -- N/A 15th -- N/A 16th -- N/A 17th -- N/A 18th -- N/A 19th -- N/A 20th -- N/A 21th -- N/A 22th -- N/A 23th -- N/A 24th -- N/A 25th -- N/A 26th -- N/A 27th -- N/A 28th -- N/A 29th -- N/A 30th -- N/A 31th -- N/A 32th -- N/A 33th -- N/A 34th -- N/A 35th -- N/A 36th -- N/A 37th -- N/A 38th -- N/A 39th -- N/A 40th -- N/A THD 1.8215 23 PWHD 4.4841 23 Note: Three phase equipment. www.tuv.com Page 18 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 Photo: Overall view Front view www.tuv.com Page 19 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 Side view Back view www.tuv.com Page 20 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 Bottom view 1 (for model Solis-3P12K-4G,Solis-3P15K-4G,Solis-3P17K-4G,Solis-3P20K-4G) Bottom view 2 (for model Solis-3P5K-4G,Solis-3P6K-4G,Solis-3P8K-4G,Solis-3P9K-4G, Solis- 3P10K-4G) www.tuv.com Page 21 of 21 Report No.: 50286745 001 MS-0024873-appendix 17 V.0 Inside view - End of report- 2019-08-28T15:14:35+0800 Yin Yue 2019-08-28T15:46:17+0800 John Dai 2019-08-28T07:46:51+0000