Logo Passei Direto
Buscar
Material
páginas com resultados encontrados.
páginas com resultados encontrados.

Prévia do material em texto

Produkte 
Products 
 
 
 
Prüfbericht - Nr.: 
Test Report No.: 
50286745 001 Auftrags-Nr.: 
Order No.: 
244165550 Seite 1 von 21 
Page 1 of 21 
Kunden-Referenz-Nr.: 
Client Reference No.: 
1616910 Auftragsdatum: 
Order date: 
30.07.2019 
Auftraggeber: 
Client: 
Ningbo Ginlong technologies Co., Ltd. 
No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, Ningbo, zhejiang, 
315712, P.R. China 
Prüfgegenstand: 
Test item: 
Grid-connected PV Inverter 
Bezeichnung / Typ-Nr.: 
Identification / Type No.: 
Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G, Solis-3P10K-4G, 
Solis-3P12K-4G, Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G 
Auftrags-Inhalt: 
Order content: 
Test report 
Prüfgrundlage: 
Test specification: 
IEC 61000-3-12: 2011 
Wareneingangsdatum: 
 Date of receipt:: 
04.08.2019 
 
Prüfmuster-Nr.: 
Test sample No.: 
A000969098-001 
Prüfzeitraum: 
Testing period: 
05.08.2019 – 09.08.2019 
Ort der Prüfung: 
Place of testing: 
TÜV Rheinland (Shanghai) Co., Ltd. 
Prüflaboratorium: 
Testing Laboratory: 
TÜV Rheinland (Shanghai) Co., Ltd. 
Prüfergebnis*: 
Test Result*: 
Pass 
geprüft/ tested by: kontrolliert/ reviewed by: 
 
 Aug.,26, 2019 John Dai / PE Aug.,26, 2019 Yin Yue / Reviwer 
 Datum 
Date 
Name/Stellung 
Name/Position 
Unterschrift 
Signature 
 Datum 
Date 
Name/Stellung 
Name/Position 
Unterschrift 
Signature 
 
Sonstiges/ Other Aspects: 
 See the following pages for General product information and comment. 
Zustand des Prüfgegenstandes bei Anlieferung: 
Condition of test item at delivery: 
Prüfmuster vollständig und unbeschädigt 
Test item complete and undamaged 
* Legende: 1 = sehr gut 2 = gut 3 = bef riedigend 4 = ausreichend 5 = mangelhaf t 
 P(ass) = entspricht o.g. Prüfgrundlage(n) F(ail) = entspricht nicht o.g. 
Prüf grundlage(n) 
N/A = nicht anwendbar N/T = nicht getestet 
Legend: 1 = very good 2 = good 3 = satisfactory 4 = sufficient 5 = poor 
 P(ass) = passed a.m. test specification(s) F(ail) = failed a.m. test specification(s) N/A = not applicable N/T = not tested 
Dieser Prüfbericht bezieht sich nur auf das o.g. Prüfmuster und darf ohne Genehmigung der Prüfstelle nicht auszugsweise vervi elfältigt 
werden. Dieser Bericht berechtigt nicht zur Verwendung eines Prüfzeichens. 
This test report only relates to the a. m. test sample. Without permission of the test center this test report is not permitt ed to 
be duplicated in extracts. This test report does not entitle to carry any test mark. 
V04 
TUV Rheinland (Shanghai) Co., Ltd. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jingan District, Shanghai 200072, P.R. 
China Tel. : +86 21 61081188 Fax : +86 21 61081199 Mail: service@cn.tuv.com Web: www.tuv.com 
 
 
 
 
 
 
 
Electromagnetic Compatibility (EMC) 
Part 3-12: Limits-Limits for 
harmonic current produced by equipment 
connected to public low-voltage systems with 
 input current > 16A and ≤75A per phase 
 
Report Reference No. ................. : 50286745 001 
Tested by (name + signature)....... : See cover page .............................................. 
Witnessed by (name + signature).. : See cover page .............................................. 
Supervised by (name + signature). : See cover page .............................................. 
Approved by (name + signature) ... : See cover page .............................................. 
Date of issue ............................. : See cove page 
Testing Laboratory...................... : TÜV Rheinland (Shanghai) Co., Ltd. 
Address .................................... : No. 177, Lane 777 West Guangzhong Road, Jingan District, 
Shanghai, P.R.China 
Testing location/ procedure .......... : CBTL TMP WMT SMT RMT CCATL 
Testing location/ address ............. : TÜV Rheinland (Shanghai) Co., Ltd. 
No. 177, Lane 777 West Guangzhong Road, Jingan District, 
Shanghai, P.R.China 
Applicant’s name ........................ : Ningbo Ginlong technologies Co., Ltd. 
Address .................................... : No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, 
Ningbo, zhejiang, 315712, P.R. China 
Test specification: 
Standard ................................... : IEC 61000-3-12: 2011 
Test procedure........................... : TR 
Non-standard test method………..: N/A 
Test Report Form No. ................. : MS-0024873-appendix 17 V.0 
Test Report Form(s) Originator ..... : TÜV Rheinland Group 
Master TRF ............................... : 2017-08 
Test item description ................... : Grid-connected PV Inverter 
Trade Mark................................ : 
 
Manufacturer ............................. : Same as the applicant 
Model/Type reference ................. : Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, 
Solis-3P9K-4G,Solis-3P10K-4G, Solis-3P12K-4G, 
Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G 
Ratings ..................................... : See copy of marking plate for details 
 
 
www.tuv.com 
 
 
 Page 3 of 21 
 
 Report No.: 50286745 001 
 
TRF No. MS-0024873-appendix 17 V.0 
 
Equipment mobility ............................................ : movable hand-held 
 stationary fixed 
Connection to the mains ..................................... : pluggable equipment direct plug-in 
 permanent connection for building-in 
Operating condition............................................ : continuous short-time intermittent 
Over voltage category Mains ............................... : OVC I OVC II OVC III OVC IV 
Over voltage category PV ................................... : OVC I OVC II OVC III OVC IV 
Mains supply tolerance (%) ................................. : -- 
Tested for IT power systems .............................. : Yes No 
IT testing, phase-phase voltage (V) ..................... : N/A 
Class of equipment ........................................... : Class I Class II 
 Class III Not classified 
Mass of equipment (kg) ...................................... : -- 
Pollution degree ................................................ : PD 1 PD 2 PD 3 
IP protection class ............................................ : IP65 
Possible test case verdicts: 
- test case does not apply to the test object ............. : N/A 
- test object does meet the requirement .................. : Pass (P) 
- test object does not meet the requirement ............. : Fail (F) 
Testing: 
Date of receipt of test items ................................. : See cover page 
Date(s) of performance of tests ............................. : See cover page 
 
 
 
 Page 4 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
General remarks 
” The test result presented in this report relate only to the object(s) tested. 
 
This report shall not be reproduced, except in full, without the written approval of the Issuing testing 
laboratory. 
"(see remark #)" refers to remark appended to the report. 
"(see Annex #)" refers to an annex appended to the report. 
Throughout this report a point is used as the decimal separator. 
 
General product information: 
 
The PCEs under test models Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G, Solis-3P10K-
4G, Solis-3P12K-4G, Solis-3P15K-4G, Solis-3P17K-4G, Solis-3P20K-4G are three-phase grid connected 
inverter for solar power generation. The Grid-connected PV Inverter utilize the advanced power conversion 
technology IGBT to convert the DC power normally from the photovoltaic array to stable three-phase AC 
power and then feed the power to the utility grid. 
 
Block diagram: 
 
 
 
 
 
 
 
 
www.tuv.com 
 
 
 Page 5 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
Model list 
 
MODELS LIST Solis-3P5K-4G Solis-3P6K-4G Solis-3P8K-4G 
IN
P
U
T
 
VMAX PV[Vdc] 1000 
ISC PV [A] 17.2+17.2 
MPP Voltage Range VMPP[Vdc] 160-850 160-850 160-850 
Max. Input Current Imax [A] 11+11 11+11 11+11 
MPP Full Pow er Voltage Range [Vdc] 230-850 280-850 370-850 
Start PV Voltage [Vdc] 180 180 180 
Backfeed Current [A] 0 0 0 
Overvoltage Category (OVC) II 
O
U
T
P
U
T
 
Rated Output Voltage Ur [Vac] 400V 
Rated Output Frequency FNETZ [Hz] 50/60 
Rated Output Pow er PE [W] 5000 6000 8000 
Max. Output Pow er PEmax [W] 5500 6600 8800 
Max. Output Current Imax [A] 7.9 9.5 12.7 
Pow er Factor cosφ [λ] [-0.8, 0.8] 
Night Pow er Consumption [W] <1 
THD [V / I] (100% full pow er) < 3% 
Acoustic Noise [dB] < 30 
Overvoltage Category (OVC) III 
S
Y
S
T
E
M
 
Protective Class I 
Enclosure Protection (IP) IP65 
Operating Temperature Range [ºC] -25 to +60 
Pollution degree (PD) PD 2 
Altitude [m] 2000 
Array Insulation Resistance Detection [Ω] 80k 
The accuracy of resistance measurement [%] < 10 
Weight [kg] 17.3 17.3 18.0 
Size [mm] 563W*310H*219D 
 Firmw are version LCD: 05 
DSP: 18 
 
 
 
 
 
www.tuv.com 
 
 
 Page 6 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
MODELS LIST Solis-3P9K-4G Solis-3P10K-4G 
IN
P
U
T
 
VMAX PV [Vdc] 1000 
ISC PV [A] 17.2+17.2 
MPP Voltage Range VMPP[Vdc] 160-850 160-850 
Max. Input Current Imax [A] 11+11 11+11 
MPP Full Pow er Voltage Range [Vdc] 415-850 465-850 
Start PV Voltage [Vdc] 180 180 
Backfeed Current [A] 0 0 
Overvoltage Category (OVC) II 
O
U
T
P
U
T
 
Rated Output Voltage Ur [Vac] 400V 
Rated Output Frequency FNETZ [Hz] 50/60 
Rated Output Pow er PE [W] 9000 10000 
Max. Output Pow er PEmax [W] 9900 11000 
Max. Output Current Imax [A] 14.3 15.9 
Pow er Factor cosφ [λ] [-0.8, 0.8] 
Night Pow er Consumption [W] <1 
THD [V / I] (100% full pow er) < 3% 
Acoustic Noise [dB] < 30 
Overvoltage Category (OVC) III 
S
Y
S
T
E
M
 
Protective Class I 
Enclosure Protection (IP) IP65 
Operating Temperature Range [ºC] -25 to +60 
Pollution degree (PD) PD 2 
Altitude [m] 2000 
Array Insulation Resistance Detection [Ω] 80k 
The accuracy of resistance measurement 
[%] 
< 10 
Weight [kg] 18.0 18.0 
Size [mm] 563W*310H*219Dmm 
 Firmw are version LCD: 05 
DSP: 18 
 
 
 
 
www.tuv.com 
 
 
 Page 7 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
MODELS LIST Solis -3P12K-4G Solis -3P15K-4G 
IN
P
U
T
 
VMAX PV [Vdc] 1000 
ISC PV [A] 34.3+34.3 
MPP Voltage Range VMPP[Vdc] 160-850 160-850 
Max. Input Current Imax [A] 22+22 22+22 
MPP Full Pow er Voltage Range [Vdc] 280-850 350-850 
Start PV Voltage [Vdc] 180 180 
Backfeed Current [A] 0 0 
Overvoltage Category (OVC) II 
O
U
T
P
U
T
 
Rated Output Voltage Ur [Vac] 400V 
Rated Output Frequency FNETZ [Hz] 50/60 
Rated Output Pow er PE [W] 12000 15000 
Max. Output Pow er PEmax [W] 13200 16500 
Max. Output Current Imax [A] 19.1 23.8 
Pow er Factor cosφ [λ] [-0.8, 0.8] 
Night Pow er Consumption [W] <1 
THD [V / I] (100% full pow er) < 3% 
Acoustic Noise [dB] < 30 
Overvoltage Category (OVC) III 
S
Y
S
T
E
M
 
Protective Class I 
Enclosure Protection (IP) IP65 
Operating Temperature Range [ºC] -25 to +60 
Pollution degree (PD) PD 2 
Altitude [m] 2000 
Array Insulation Resistance Detection [Ω] 80k 
The accuracy of resistance measurement 
[%] 
< 10 
Weight [kg] 18.9 18.9 
Size [mm] 563W*310H*219D 
 Firmw are version LCD: 05 
DSP: 18 
 
 
 
 
www.tuv.com 
 
 
 Page 8 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
MODELS LIST Solis -3P17K-4G Solis -3P20K-4G 
IN
P
U
T
 
VMAX PV [Vdc] 1000 
ISC PV [A] 34.3+34.3 
MPP Voltage Range VMPP[Vdc] 160-850 160-850 
Max. Input Current Imax [A] 22+22 22+22 
MPP Full Pow er Voltage Range [Vdc] 395-850 465-850 
Start PV Voltage [Vdc] 180 180 
Backfeed Current [A] 0 0 
Overvoltage Category (OVC) II 
O
U
T
P
U
T
 
Rated Output Voltage Ur [Vac] 400V 
Rated Output Frequency FNETZ [Hz] 50/60 
Rated Output Pow er PE [W] 17000 20000 
Max. Output Pow er PEmax [W] 18700 22000 
Max. Output Current Imax [A] 27 31.8 
Pow er Factor cosφ [λ] [-0.8, 0.8] 
Night Pow er Consumption [W] <1 
THD [V / I] (100% full pow er) < 3% 
Acoustic Noise [dB] < 30 
Overvoltage Category (OVC) III 
S
Y
S
T
E
M
 
Protective Class I 
Enclosure Protection (IP) IP65 
Operating Temperature Range [ºC] -25 to +60 
Pollution degree (PD) PD 2 
Altitude [m] 2000 
Array Insulation Resistance Detection [Ω] 80k 
The accuracy of resistance measurement 
[%] 
< 10 
Weight [kg] 19.8 19.8 
Size [mm] 563W*310H*219D 
 Firmw are version LCD: 05 
DSP: 18 
 
Factory: 
Ningbo Ginlong technologies Co., Ltd. 
No.57 Jintong Road, Binhai, (seafront) industrial Park, Xiangshan, Ningbo, zhejiang, 315712, P.R. China 
 
 
 
 
www.tuv.com 
 
 
 Page 9 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
Summary of testing: 
Tests performed (name of test and test clause) 
 
Clause(s) Test(s) Model(s) 
cl. 4.2 Harmonic current 
measurement 
Solis-3P20K-4G 
 
 
Testing location: 
All tests as described in Test Case and 
Measurement Sections were performed 
at the laboratory described on page 2. 
 
 
 
 
www.tuv.com 
 
 
 Page 10 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
Copy of marking plate: 
 
 
 
www.tuv.com 
 
 
 Page 11 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
 
www.tuv.com 
 
 
 Page 12 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
 
www.tuv.com 
 
 
 Page 13 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
 
www.tuv.com 
 
 
 Page 14 of 21 
 
Report No: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
 
 
 
www.tuv.com 
 
 
 Page 15 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
IEC 61000-3-12: 2011 
Clause Requirement – Test Result - Remark Verdict 
4 Measurement conditions p 
4.1 The average r.m.s input current shall be 
measured using the averaging method 
defined in 4.2.2 for harmonic current. 
 P 
 The manufacture may specify any value of 
r.m.s. current which is within ± 10% of the 
actual measured value and use it as the 
reference current. 
 P 
 If the value of the average r.m.s. input current 
found by measurement during these emission 
tests, measured according to the terms of this 
clause , is not less than 90% nor greater 
than110% of the value of current specified by 
manufacture. 
 P 
4.2 Harmonic current measurement P 
4.2.1 The harmonic current limits for equipment as 
specified apply to the line currents for all 
types of power connections and load. 
 P 
4.2.2 The measurement of harmonic current shall 
be performance as follows: 
- For each harmonic order, measure 
1.5s smooth r.m.s. harmonic current 
in each discrete fourier time winding 
as defined in IEC 61000-4-7. 
- For each harmonic order, calculate 
the arithmetic average of the 
measured value from the DFT time 
windows, over the entire test 
observation period as defined in 
4.2.7. 
 P 
4.2.3 The repeatability of the average value for the 
individual harmonic current over the entire 
test abservation period shall be better than 
±5% of the applicable limit. 
 P 
4.2.4 Equipment is operation or is taken out of 
operation manually or automatically, harmonic 
currents are not taken into account for the first 
10s, or until the equipment is fully in or out of 
operation. 
 P 
4.2.5 The average value for the individual harmonic 
currents, taken over the entire test 
observation period shall be less than or equal 
to the applicable limits in table 2 to 5. 
 P 
5 Requirements and limits for equipment P 
5.1 Only symmetrical control methods are 
allowed under normal operation conditions. 
 P 
5.2 The limits given apply to 230/240V, 50Hz 
systems, The limits for the other systems will 
be added in a future edition of this standard. 
 P 
6 Product documentationP 
 
 
www.tuv.com 
 
 
 Page 16 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
IEC 61000-3-12: 2011 
Clause Requirement – Test Result - Remark Verdict 
7 Test and simulation conditions P 
7.1 Conformity with this standard may be 
determined by either of the two methods as 
follows: 
a) Direct measurement (see 7.2) 
b) Calculation by validated simulation 
(see 7.3) 
 P 
7.2 The requirements for the measurement 
instrumentation are given in IEC 61000-4-7. 
 P 
7.3 Requirements for simulation P 
7.4 General conditions for test and simulation P 
Annex A Type test conditions P 
Annex B Illustration of limits for harmonic currents P 
Annex C Equipment not complying with the 
requirements and limit of this standard 
 N/A 
Annex D Information on the PWHD factor P 
Bibliography -- N/A 
 
 
 
 
www.tuv.com 
 
 
 Page 17 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
4.2 Harmonic current (Solis-3P20K-4G) P 
Watts 20000W 
VA 20000VA 
Vrms 400V 
Arms 28.9A 
PF 1.00 
Frequency(Hz) 50 
Harmonic Measurement value(%) Limit (%) 
2nd 0.5164 8 
3rd 0.5312 21.6 
4th 0.4949 4.00 
5th 0.9133 10.70 
6th 0.2351 2.67 
7th 0.6774 7.20 
8th 0.2632 2.00 
9th 0.1361 3.80 
10th 0.1362 1.60 
11th 0.2580 3.10 
12th 0.1525 1.33 
13th 0.3749 2.00 
14th -- N/A 
15th -- N/A 
16th -- N/A 
17th -- N/A 
18th -- N/A 
19th -- N/A 
20th -- N/A 
21th -- N/A 
22th -- N/A 
23th -- N/A 
24th -- N/A 
25th -- N/A 
26th -- N/A 
27th -- N/A 
28th -- N/A 
29th -- N/A 
30th -- N/A 
31th -- N/A 
32th -- N/A 
33th -- N/A 
34th -- N/A 
35th -- N/A 
36th -- N/A 
37th -- N/A 
38th -- N/A 
39th -- N/A 
40th -- N/A 
THD 1.8215 23 
PWHD 4.4841 23 
Note: 
Three phase equipment. 
 
 
 
 
www.tuv.com 
 
 
 Page 18 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
Photo: 
 
 
 
Overall view 
 
 
Front view 
 
 
 
 
www.tuv.com 
 
 
 Page 19 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
Side view 
 
 
 
Back view 
 
 
 
 
 
 
 
 
 
 
 
www.tuv.com 
 
 
 Page 20 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
 
Bottom view 1 (for model Solis-3P12K-4G,Solis-3P15K-4G,Solis-3P17K-4G,Solis-3P20K-4G) 
 
 
 
Bottom view 2 (for model Solis-3P5K-4G,Solis-3P6K-4G,Solis-3P8K-4G,Solis-3P9K-4G, Solis-
3P10K-4G) 
 
 
www.tuv.com 
 
 
 Page 21 of 21 
 
Report No.: 50286745 001 
 
MS-0024873-appendix 17 V.0 
 
 
Inside view 
 
 
- End of report- 
 
		2019-08-28T15:14:35+0800
	Yin Yue
		2019-08-28T15:46:17+0800